Camlock Sandwich Panels for Cold Room Walls and Ceilings
A camlock sandwich panel has a built-in male-female cam-lock mechanism. Turning the cam with a hex key hooks the male lock into the female lock and pulls the two panels firmly together, so wall and ceiling panels interlock without gaps and the use of adhesives is kept to a minimum. Panels have a PUR or PIR insulation core and can be dismantled, moved and re-installed easily.
Technical Specifications
| Feature | Specification |
|---|---|
| Core | PUR (polyurethane) or PIR (polyisocyanurate) rigid foam, 42 kg/m³ (±2) density |
| Thickness | 80, 100, 120, 150 and 200 mm |
| Panel width | 1110 mm or 1135 mm |
| Joint | Male-female cam lock, tongue-and-groove edge, mastic in joint gaps |
| Skins | 0.50 mm painted galvanized steel sheet, RAL 9002; stainless steel, PVC or PPGI depending on use |
| Surface | Flat or corrugated, with protective film during transport and assembly |
| Use | Cold room walls and ceilings, rooms with panels longer than 9 m |
Thickness Selection
| Thickness | Weight | U-value | Recommended use |
|---|---|---|---|
| 80 mm | 12.22 kg/m² | 0.28 W/m²K | Chill rooms, 0 to +5 °C |
| 100 mm | 13.20 kg/m² | 0.22 W/m²K | Low chill and light freeze, −5 to −10 °C |
| 120 mm | 14.00 kg/m² | 0.19 W/m²K | Freezer rooms, to −15 °C |
| 150 mm | 15.31 kg/m² | 0.14 W/m²K | Deep freeze, −18 to −35 °C |
| 200 mm | 17.20 kg/m² | 0.11 W/m²K | Blast freezers, −40 °C and below |
Recommended use is for an outside temperature of +35 °C and a heat gain limit of 10 W/m². Final selection depends on site climate and project conditions.
Advantages
- Fast locking: Cam locks pull panels tight together, with fast and even clamping along the joint.
- Airtight envelope: Gap-free joints plus mastic give a sealed, energy-efficient cold room.
- Vacuum resistant: Walls and ceilings act as one unit against pressure and vacuum loads.
- Tall rooms: Panels over 9 m without extra steel profiles in the wall.
- Corrosion-proof lock: No seizing of the lock due to corrosion over the life of the room.
- Demountable: Rooms can be dismantled, moved and re-installed easily.
Installation Steps
- Prepare a level, insulated floor and set out the room according to the panel layout.
- Stand the first wall panel, then offer the next panel up so the male and female locks face each other.
- Apply mastic to the gaps in the joint.
- Turn each cam with the hex key to pull the panels together, and close the lock holes with caps.
- Lay the ceiling panels on the wall panels and lock them the same way; hang long spans from the structure.
- Finish corners and joints with profiles and food-safe silicone.
Where It Is Used
Fruit and vegetable facilities, dairy and ice cream facilities, poultry processing plants, meat plants, cold storage warehouses and fish processing and storage areas.
See also our sandwich panels, floor panels and industrial cold rooms.
Frequently Asked Questions
What is a camlock sandwich panel?
An insulated cold room panel with a built-in male-female cam lock, which clamps panels tightly together with a hex key.
Which thicknesses are available?
80, 100, 120, 150 and 200 mm.
Can the panels be dismantled?
Yes. Rooms can be dismantled, moved and re-installed easily.
Request a Quote
Send us the room dimensions, room temperature, panel thickness and project location.